NBC(AE) 2023 · 9.25.3 and 9.36.2.9 / 9.36.2.10

Two different air barrier numbers, and most pages quote them interchangeably.

Search for Canadian air barrier requirements and you will find 0.02 L/(s·m²) at 75 Pa quoted everywhere, usually with no indication of what is being tested. That figure is real and it is Alberta’s — it is the MATERIAL criterion in CAN/ULC-S741. It is not the ASSEMBLY figure, which is 0.20 L/(s·m²) under CAN/ULC-S742. Ten times apart, routinely conflated. And NBC(AE) 2023 Article 9.25.3.2 itself carries no number at all — it is performance-worded, and the threshold arrives through 9.36.2.10.(1).

Sources last checked

Section 01

Material vs assembly — the two numbers, and which one 0.02 is

Material

The single product providing the principal resistance to air leakage. Published product results are reported to ASTM E2178.

Limit at 75 Pa
≤ 0.02 L/(s·m²)
Standard
CAN/ULC-S741

NBC(AE) · 9.36.2.10.(1)

Assembly — Part 9 (S742 route)

Limit at 75 Pa
≤ 0.20 L/(s·m²)
Standard
CAN/ULC-S742, Type A4

NBC(AE) · 9.36.2.9.(1)(b)

Assembly — Part 9 (E2357 route)

Conditional: sustained wind loads on a 1-in-50 hourly wind pressure basis not exceeding 0.65 kPa, and the assembly on the warm side of the insulation.

Limit at 75 Pa
≤ 0.20 L/(s·m²)
Standard
ASTM E2357

NBC(AE) · 9.36.2.9.(1)(c)

Assembly — Part 3 commercial

Limit at 75 Pa
≤ 0.20 L/(s·m²)
Standard
CAN/ULC-S742

NECB 2020 · 3.2.4.3

Whole building — Part 3 commercial

A third scale again, and an option rather than a mandate — see Section 06.

Limit at 75 Pa
≤ 1.50 L/(s·m²)
Standard
ASTM E3158

NECB 2020 · 3.2.4.2

The air leakage limits that apply in Alberta, sorted by what is actually being tested. All at 75 Pa.

Section 02

What NBC(AE) 9.25.3 actually says

9.25.3.2.(1)
“Air barrier systems shall possess the characteristics necessary to provide an effective barrier to air infiltration and exfiltration under differential air pressure due to stack effect, mechanical systems or wind.”

National Building Code – 2023 Alberta Edition — 9.25.3.2.(1)

Performance-worded, end to end. No permeance figure, no test pressure, no standard named in this Article. This is a requirement about what the system must do, and it is assessed accordingly. A full-document search of the Alberta edition for “0.02 L/(s” returns no hit anywhere in Subsection 9.25.3 — so a specification that cites 9.25.3.2 as the source of a numeric limit is citing the wrong clause, even though the number itself is right.

The preceding Article sets the purpose. Article 9.25.3.1.(1) requires assemblies separating conditioned from unconditioned space or from the ground to include an air barrier system providing a continuous barrier to air leakage — outward, to prevent excessive moisture condensation in wall, floor, attic or roof spaces during winter; and inward, to prevent room-side condensation, ensure comfort, and minimise the ingress of soil gas. NBC(AE) · 9.25.3.1.(1)

Continuity is handled in Article 9.25.3.3: panel-type joints sealed; flexible sheet joints sealed, or lapped not less than 100 mm and clamped. NBC(AE) · 9.25.3.3

Section 03

Where the material threshold lives

9.36.2.10.(1)
“Materials intended to provide the principal resistance to air leakage shall conform to CAN/ULC-S741, ‘Standard for Air Barrier Materials – Specification.’”

National Building Code – 2023 Alberta Edition — 9.36.2.10.(1)

This is the hook. The material criterion is not written into the building-envelope subsection at all — it arrives through the energy-efficiency section, by reference to a standard. CAN/ULC-S741 is what sets the ≤ 0.02 L/(s·m²) at 75 Pa material criterion, and it applies to the material providing the principal resistance to air leakage — one product, not the wall it sits in.

The assembly criterion arrives the same way, one Article earlier: 9.36.2.9.(1)(b) references CAN/ULC-S742, “Standard for Air Barrier Assemblies – Specification,” and it is that standard’s Type A4 classification — ≤ 0.20 L/(s·m²) at 75 Pa — that a tested assembly has to reach. NBC(AE) · 9.36.2.9.(1)(b)

Both standards are published by ULC and are paywalled, which is a large part of why the two numbers circulate detached from what they measure. The clause numbers above are free to read; the standards behind them are not.

Section 04

Three routes to airtightness compliance under 9.36.2.9

(a) System route

What it requires
A continuous air barrier system per Subsection 9.25.3, with materials conforming to CAN/ULC-S741 per 9.36.2.10.

NBC(AE) · 9.36.2.9.(1)(a)

(b) Assembly route — S742

What it requires
That, plus a building assembly with air leakage ≤ 0.20 L/(s·m²) — Type A4 — tested to CAN/ULC-S742 at 75 Pa.

NBC(AE) · 9.36.2.9.(1)(b)

(c) Assembly route — ASTM E2357

What it requires
That, plus an assembly ≤ 0.20 L/(s·m²) tested to ASTM E2357, provided sustained wind loads on a 1-in-50 hourly wind pressure basis do not exceed 0.65 kPa and the assembly sits on the warm side of the insulation.

NBC(AE) · 9.36.2.9.(1)(c)

The three compliance routes in Sentence 9.36.2.9.(1). Any one of them satisfies the requirement.

Note that route (a) is the material route on its own. Under (a) no assembly test is required at all — a continuous system built to 9.25.3 out of S741-conforming materials satisfies the Article. The 0.20 figure only becomes a requirement if a designer elects route (b) or (c). That is the second half of the conflation problem: the assembly number is frequently written into specifications as though it were mandatory, when it is one of three alternatives.

Route (c) has a location gate, and Red Deer clears it. NECB Table C-1 gives Red Deer a 1-in-50 hourly wind pressure of 0.40 kPa, comfortably below the 0.65 kPa ceiling in 9.36.2.9.(1)(c)(i). Whether the route applies to a given project is the designer’s and the authority’s call; the 0.40 kPa is code-table fact. NECB 2020 · Table C-1

Two further sentences govern how the system is built:

  • The air barrier system shall be continuous across construction, control and expansion joints, across junctions between different materials and assemblies, and around penetrations through all building assemblies. NBC(AE) · 9.36.2.9.(2)
  • Where the airtight material sits toward the exterior, its location and properties must conform to Subsection 9.25.5 — the outboard-to-inboard thermal resistance ratio rule. That is the clause that catches exterior foam, and it is set out on the vapour barrier page. NBC(AE) · 9.36.2.9.(6)

Section 05

Where closed-cell foam lands against the material threshold

CAN/ULC-S705.1 makes air permeance of ≤ 0.020 L/(s·m²) a mandatory material property for medium-density closed-cell foam — so a conforming product clears the S741 material criterion by definition of its own material standard. Published product results sit an order of magnitude below it. CCMC technical criteria · CAN/ULC-S705.1

CAN/ULC-S741 / S705.1 material criterion

Air permeance
≤ 0.020 L/(s·m²) @ 75 Pa
At thickness
—

NBC(AE) · 9.36.2.10.(1) → S741

BASF WALLTITE XL01

Air permeance
0.0022 L/(s·m²)
At thickness
25 mm

CCMC 14230-R

Elastochem Insulthane Extreme

Tested to ASTM E2178. Separately, the product's air barrier ASSEMBLY is classified A1 under CAN/ULC-S742 at below 0.05 L/(s·m²) — a different test, a different number, and the distinction this page exists to make.

Air permeance
0.002 L/(s·m²)
At thickness
25 mm

Elastochem technical guide

Huntsman Sealection 500 (open-cell)

Open-cell reaches the material threshold, but at three and a half times the thickness — and its published water vapour permeance at that thickness is 362 ng/(Pa·s·m²), against the 60 ng/(Pa·s·m²) vapour barrier limit in NBC(AE) 9.25.4.2.(1).

Air permeance
< 0.02 L/(s·m²)
At thickness
89 mm (3.5 in.)

Sealection 500 TDS

Published air permeance results against the MATERIAL criterion of 0.020 L/(s·m²). Lower is tighter. None of these are assembly results.

Municipal enforcement in Alberta is real and worth reading before specifying. Rocky View County’s spray foam guideline requires a CCMC listing, a certified installer and a product label at the electrical panel — and where a non-CCMC-listed product is used as an air or vapour barrier, it requires a building-envelope P.Eng. report against NBC(AE) 9.25.3 and 9.25.4. Rocky View County guideline

Section 06

Part 3 commercial — NECB 2020 Subsection 3.2.4

Commercial work is governed by a different subsection with a third scale of number. Article 3.2.4.1.(1) requires the envelope to be designed and constructed with a continuous air barrier system by complying with either 3.2.4.2 or 3.2.4.3 — two routes, not a single mandate.

Whole-building test route

Tested to ASTM E3158, building prepared per the standard's building-envelope test, tested both pressurised and depressurised, and the two measured rates averaged. Leakage area includes all surfaces separating conditioned from unconditioned space.

Limit
1.50 L/(s·m²)

NECB 2020 · 3.2.4.2

Assembly route

Assemblies conforming to CAN/ULC-S742, or designed and evaluated to provide the principal resistance to air leakage, designed using the 1-in-50 hourly wind pressure for the location, with at least one material conforming to CAN/ULC-S741.

Limit
0.20 L/(s·m²)

NECB 2020 · 3.2.4.3

Curtain walls; fixed windows and skylights

Limit
0.2 L/(s·m²)

NECB 2020 · 3.2.4.3

Operable windows and skylights; doors

Limit
0.5 L/(s·m²)

NECB 2020 · 3.2.4.3

Overhead doors

ANSI/DASMA 105 or ASTM E283. The number that matters most in a shop or warehouse.

Limit
2.0 L/(s·m²)

NECB 2020 · 3.2.4.3

Revolving and automatic sliding doors; main entry doors

Main entry doors at this limit where total area is ≤ 2% of gross wall area.

Limit
5.0 L/(s·m²)

NECB 2020 · 3.2.4.3

Loading docks interfacing with truck boxes

Sentence (10) requires seals between the truck box and the building — an explicit requirement that is routinely value-engineered out.

Limit
Weather seals required

NECB 2020 · 3.2.4.3.(10)

NECB 2020 air leakage compliance routes and component limits, at 75 Pa.

Note that the assembly route in 3.2.4.3 still requires at least one material conforming to CAN/ULC-S741. The material criterion does not go away on a Part 3 building; it sits underneath the assembly number, exactly as it does in Part 9. NECB 2020 · 3.2.4.3

Section 07

Testing is optional in Alberta — which makes a measured result worth something

The Part 9 position is the same in substance. On the prescriptive path, no test is required. On the performance path, Alberta’s amended Sentence 9.36.5.10.(9) lets the modeller assume 2.5 ACH50 at a pressure exponent of 0.67 where the air barrier system is built per Subsection 9.25.3 and Articles 9.36.2.9 and 9.36.2.10 — or use a tested value. A test is needed only to claim something better than the default. STANDATA 23-BCB-001

That is worth reading as an opportunity rather than a loophole. Because the test is optional, a measured result is a real differentiator — and the code supplies the vocabulary for it. The Airtightness Levels in Table 9.36.6.4.-A give a project a code-defined badge: AL-1A at 2.5 ACH50, AL-2A at 2.0, AL-3A at 1.5, AL-4A at 1.0, AL-5A at 0.6. “This house tested at AL-3A” is a considerably stronger statement than “we sealed it well.” NBC(AE) · Table 9.36.6.4.-A

Two testing details that get conflated in Canadian content, worth stating precisely while we are here. The current test method is CAN/CGSB-149.10-2019, which supersedes the 149.10-M86 edition most web pages still cite. CAN/CGSB-149.10-2019 And CSA F326 is not an airtightness test standard — in the NBC it appears as CAN/CSA-F326-M, Residential Mechanical Ventilation Systems. Different document, different subject. NBC · CAN/CSA-F326-M (referenced documents)

Section 08

Sentences to strike from an Alberta specification

  • “Air barrier assemblies shall not exceed 0.02 L/(s·m²) at 75 Pa.” Wrong by a factor of ten. 0.02 is the material criterion in CAN/ULC-S741, reached through 9.36.2.10.(1). The assembly criterion is 0.20 L/(s·m²) — Type A4 under CAN/ULC-S742, per 9.36.2.9.(1)(b). Specifying the material number at the assembly level asks for a wall no tested assembly classification exists for.
  • “NBC(AE) 9.25.3.2 requires air barrier materials to test at or below 0.02 L/(s·m²) at 75 Pa.” The number is right; the clause is not. Article 9.25.3.2 is performance-worded and carries no figure. Cite 9.36.2.10.(1) and CAN/ULC-S741 instead — that is the citation that survives a plan-review question.
  • “A tested air barrier assembly is required.” Not on its own. Sentence 9.36.2.9.(1) offers three routes, and route (a) — a continuous system per 9.25.3 built from S741-conforming materials — requires no assembly test at all.
  • “Alberta requires a blower door test on commercial buildings.” NECB 2020 offers whole-building testing as one of two routes.
  • “Contractor shall be CUFCA-licensed.” There are four CCMC-recognised site quality assurance programmes — CUFCA, Caliber, BPC and UFC — and each manufacturer designates one for its product. A spec naming a single body excludes every contractor spraying a product designated to one of the other three, which is most of the Canadian market. The National Master Construction Specification was revised for exactly this reason: the previous version referenced only one of the four and created “quality assurance compliance confusion in the building industry.” The workable wording is “licensed under a CCMC-recognised site quality assurance programme (CUFCA, Caliber, BPC or UFC), as designated by the product manufacturer.” ACC / SFC, NMS Section 07 21 29
  • Any clause requiring the contractor to hold a CCMC certification. The Canadian Construction Materials Centre evaluates and lists products, not contractors — so the requirement as written cannot be met by anyone. The checkable version is a CCMC-listed product with an active status, plus installer certification under the programme that product’s manufacturer designates. NRC CCMC 14230-R — a product evaluation report
Sources

Every number on this page, and where it came from.

Code values are transcribed from the free National Research Council electronic editions rather than from third-party summaries. Where a figure is a manufacturer's published test result rather than code text, it is labelled as such.

  1. 01

    National Building Code – 2023 Alberta Edition

    National Research Council Canada

    Subsection 9.25.3, Articles 9.36.2.9 and 9.36.2.10, Subsection 9.36.6.

    https://nrc-publications.canada.ca/eng/view/object/?id=0316d953-0d55-4311-af69-cad55efec499
  2. 02

    National Energy Code of Canada for Buildings 2020

    National Research Council Canada

    Subsection 3.2.4, Air Leakage — Articles 3.2.4.1, 3.2.4.2 and 3.2.4.3; Table C-1 for Red Deer design data.

    https://nrc-publications.canada.ca/eng/view/object/?id=af36747e-3eee-4024-a1b4-73833555c7fa
  3. 03

    NECB 2020 — significant changes

    National Research Council Canada

    NRC's own statement that whole-building airtightness testing is 'introduced as an option' for compliance.

    https://nrc.canada.ca/en/certifications-evaluations-standards/codes-canada/codes-canada-publications/national-energy-code-canada-buildings-2020
  4. 04

    STANDATA 23-BCB-001 — Energy efficiency Tier 1 of Section 9.36

    Alberta Municipal Affairs

    Alberta's single 2.5 ACH50 default, replacing the national two-level system.

    https://open.alberta.ca/dataset/5cd7e000-4f7c-4188-b26f-11a16bbe43f8/resource/37c27a63-3517-4b03-b4e2-bd2733219caa/download/ma-standata-bulletin-building-23-bcb-001-2024-04.pdf
  5. 05

    CAN/ULC-S705.1 technical criteria

    Canadian Construction Materials Centre, NRC

    The medium-density closed-cell material table, including air permeance ≤ 0.020 L/(s·m²) as a pass/fail material property.

    https://nrc.canada.ca/en/certifications-evaluations-standards/canadian-construction-materials-centre/ccmc-publications/document.html?id=CAN_ULC-S705.1-15&type=techcrit
  6. 06

    CCMC 14230-R — BASF WALLTITE XL01

    Canadian Construction Materials Centre, NRC

    Air permeance of 0.0022 L/(s·m²) at 25 mm.

    https://nrc.canada.ca/en/certifications-evaluations-standards/canadian-construction-materials-centre/ccmc-publications/document.html?id=14230-R&type=cert
  7. 07

    Insulthane Extreme Technical Guide

    Elastochem

    Air permeance 0.002 L/(s·m²) at 25 mm per ASTM E2178; air barrier system classified A1 under CAN/ULC-S742.

    https://elastochem.com/wp-content/uploads/2023/08/InsulthaneExtreme_Technical_Guide_Rev4.pdf
  8. 08

    Sealection 500 Technical Data Sheet

    Huntsman Building Solutions

    Open-cell reaching the air-barrier material threshold at 3.5 in. (89 mm), with a published water vapour permeance of 362 ng/(Pa·s·m²) at the same thickness.

    https://huntsmanbuildingsolutions.com/en-US/en-CA/sites/en_us/files/2025-06/20.00085-Sealection_500-TDS_EN-V7-DIGITAL.pdf
  9. 09

    CAN/CGSB-149.10-2019

    Canadian General Standards Board

    Determination of the airtightness of building envelopes by the fan depressurization method — the current edition, superseding 149.10-M86.

    https://publications.gc.ca/collections/collection_2019/ongc-cgsb/P29-149-010-2019-eng.pdf
  10. 10

    A Guide to Installing Medium-Density Spray Foam in Canada

    American Chemistry Council / Spray Foam Coalition

    The four CCMC-recognised site quality assurance programmes, and why NMS Section 07 21 29 was revised to name all four.

    https://www.americanchemistry.com/content/download/7153/file/A-Guide-to-Installing-Medium-Density-Spray-Foam-In-Canada.pdf
  11. 11

    Guideline — Spray Foam Insulation

    Rocky View County

    An Alberta municipal example: CCMC listing, certified installer, product label at the panel, and a building-envelope P.Eng. report where a non-listed product is used as an air/vapour barrier.

    https://www.rockyview.ca/sites/default/files/2025-06/Guideline-Spray-Foam-Insulation.pdf
Talk it through

Writing or reviewing an air barrier specification for Alberta?

Send the spec section. You'll get it checked against NBC(AE) 9.36.2.9 and 9.36.2.10, or NECB 3.2.4 for a Part 3 building — including whether each number is written at the material or the assembly level, with the clause numbers, so you can take the correction to the designer yourself.

Get a QuoteCall (403) 350-2720